  • gas pipe fixing

Gas pipe fixing 1Spotted recently on a brand-new CO2 installation: sling hangers supporting gas pipes. These should not be done. CO2 discharges at 51.7 bar, the speed and movement of the gas down the pipe can cause the pipe to move around and possibly be dislodged with this type of hanger.

All gas suppression systems operate via high-pressure pipe lines.