NON COMPLIANT
The FSIB will no longer mark the locally manufactured TECHNOSWITCH panel range as compliant on any report.
The failure of the panel to provide an alarm when the batteries are disconnected and / or removed, we believe, is unacceptable.
A CLASS WIRING
All addressable fire panels have to be wired as A class circuits in accordance with SANS 10139:2012. Please ensure all your installers are made aware of this requirement. B class wired circuits will be marked NON COMPLIANT in future reports.